MHG 231
MHG 231
Optical Smoke Detector
The MHG 231 Optical Smoke Detector is a conventional fire detector with voltage characteristics.

The MHG 231 Optical Smoke Detector is a conventional fire detector with voltage characteristics. In conjunction with the central control units of the electric fire signalling system LITES it is intended for an automatic signalling of fire occurrence as a detector responsive to fouling – to both visible and invisible smoke particles (aerosols).

The MHG 231 detector is to install at places where occurrence and concentration of smoke is assumed. The detector is responsive to fouling – to both visible and invisible smoke particles
(aerosols) – on the principles of detection of scattered infrared radiation.

The MHG 231 detector is to install in the socket MHY 734.029. It is possible to connect it to the central control units MHU 113, MHU 108, MHU 106 with the loop unit JSM-5, or to the
addressable central control units of the electric fire signalling system LITES by means of the addressing unit MHY 409. It is also possible to attach the signal lighting units MHS 409, MHS
408 (parallel signalling).

For its use in the electric fire signalling system the detector is liable to the agreement examination according to law No. 22/1997 Sb., in wording law No. 71/2000 Sb. and the relevant orders of the government.

It fulfils the requirements of the European standard specification EN 54 – 7.

 

Technical specifications
Supply voltage range 16 ÷ 24 Vss
Nominal voltage 21,5 Vss
Current at alarm mode (including optical signalling) max. 100 mA (limited by the control unit)
Operating voltage at fire alarm (5,7 ÷ 8) V at 10 mA
Optical signalling a couple of red LED (light emitting diodes)
Parallel signalling type LITES
Smoke sensitivity adjustable in three degrees
high (+) m = 0,07 ÷ 0,09 dB/m
normal (N) m = 0,09 ÷ 0,12 dB/m
low (-) m = 0,14 ÷ 0,18 dB/m (is not in accordance with EN 54-7)
Reaction time adjustable in two degrees
short (S) 5+3-2 s
long (L) 30 ± 10 s
Protection according to ČSN EN 60529 IP43
Safety requirements product intended for a plant with safety arrangement in terms of ČSN EN 60950
Radioscreening degree according to ČSN EN 55 022 B-class equipment
Dimensions (98 x 42) mm
Weight c. 140 g

 

 

Working conditions
The MHG 331 detector is intended for environments protected against weather influence, without occurrence of agressive substances, and for places where its protection and climatic immunity suits, and where sudden temperature changes leading to dew and ice accretion don`t occur.
Working temperature range -25 °C to +70 °C
Period of significant temperature (45 °C ÷ 70 °C) 2 month in a year
Relative humidity max. 95% at +40 °C
Period of significant humidity (85% ÷ 95%/£40 °C) 100 hours in a year