MHG 282 Ex
MHG 282
Optical Smoke Detector
The MHG 282 Optical Smoke Detector is designed for the automatic detection and indication of smoke of arising fire within LITES fire detection and alarm system.

The MHG 282 Optical Smoke Detector is designed for the automatic detection and indication of smoke of arising fire within LITES fire detection and alarm system.

A robustly built detector operating on the principle of infra-red light scattering on smoke particles is primarily intended for explosion and fire hazardous areas with combustible gas,fumes, dust and explosives as well. It is also well-suited for common environments where higher mechanical and weather resistance is required.

The MHG 282 Detector is available in two variants:
MHG 282.049 with voltage chatacteristic
MHG 282.050 with current characteristic

Both detector types irrespective to which kind of environment they are used for may be connected to LITES MHU l06 and MHU l08 Conventional Control Panels directly. When connected to LITES MHU l09 Addressable Control Panel the MHY 409 Addressable Unit is indispensable.

The detectors are to be connected to the fire loop wiring by means of the MHY 703 Mount Base.

The MHS 407.l23 Remote Indicator or other LITES models are also available for parallel signalling with the MHG 282.049 Detector and the MHS 407.l24 Remote Indicator to be used with the MHG 282.050 Detector version.

The detector has been approved for use by The Ministry of Internal Affairs of The Czech Republic, Head Administration of The Fire Guard Corps and meets EN 54 - 7 , ČSN EN 500l4, 500l9 and 50020 standards.

 

Technical Specifications
Supply Voltage Range (16 ÷ 24) Vss
Nominal Supply Voltage 21,5 Vss
Maximum Supply Voltage 30 Vss
Quiescent Current max. 70 µA
Alarm Current
MHG 282.049 100 mA max. *See Note bellow
MHG 282.050 20 (+1/-5) mA
Alarm Voltage (6 ÷ 8) V při 10 mA
Alarm Indication red LED
Remote Indicator  LITES Type
Response Time (3 ÷ 8) s
Smoke Sensitivity
complying EN 54-7 m = cca 0,15 dB/m (response to aerosol at tunnel test at v = 1m/s)
complying ČSN 342710 100 mg (response to burning of lime wood in 1 m3 )
IP Rating complying ČSN EN 60529  
Detector Body connected to Mount Base IP 54
Detector Sensor IP 32
Workmanship according to ČSN EN 50014, 50019 E Ex e II T6
Safety Class to ČSN 341010 III
Interference Suppression to ČSN 334200 and ČSN EN 55022  
Size of Detector dia x heigh ø147 × 71 mm
Weight cca 650 g

 

 

Working Conditions
Inner spaces with no agressive substances
Operating Temperature Range -25 °C to +70 °C
Relative Air Humidity 95% max. at 40 °C (3 x 21 days per year)
Atmosphere Pressure Range 86 až 106 kPa

 

Note: The current at alarm state is reduced automatically provided LITES control panels are used. Using other types of control panels the current is to be reduced so as not not to exceed  l00 mA.