MHG 664
MHG 664
Linear Smoke Detector
The MHG 664 interactive and autonomous linear smoke detector with servomotors for optics adjustment and laser pointer is intended for automatic fire alarm signalling as smoke detector in analogue addressable and conventional Fire Detection and Fire Alarm

The MHG 664 interactive and autonomous linear smoke detector with servomotors for optics adjustment and laser pointer is intended for automatic fire alarm signalling as smoke detector in analogue addressable and conventional Fire Detection and Fire Alarm System LITES.

It is intended to indicate a rising fire on the principle of reducing the infrared ray trough smoke particles. Linear smoke detector is placed at locations of anticipated smoke occurrence and
concentration.

Interactive Linear smoke detector MHG 664 in a reflex version is intended for up to 100m. It consists of transmitter and receiver on a printed circuit board, which is along with the optical
system placed in a plastic box with an aperture for the infrared ray. The detector is equipped with servomotors and laser pointer for optics adjustment.

To each detector is connected the Indicating preparation MHY 740. For adjustment of the detector serve the preparations MHY 536, MHY 537 or MHY 538, which also serve as a control
unit for autonomous use of the detector.

The detector operates in regimes:

  • interactive using analogue communication with C.I.E. MHU 110, MHU 111, MHU 115, MHU 116,MHU 117,
  • interactive with contact outputs Alarm and Fault for connection to conventional C.I.E.,
  • interactive with contact outputs Alarm and Fault for autonomous regime or for connection to C.I.E.of other manufacturers.

 

Technical parameters
Power supply addressable regime addressable C.I.E. LITES
  autonomous regime (10 ÷ 24) Vss
Standby current   max. 300 μA (according to range)
Fire alarm current addressable regime max. 35 mA (according to connected signalling)
  autonomous regime 40 mA at 24 VDC, 100 mA at 10 VDC
Optical signalling   red LED Alarm in indicating preparation, yellow LED Fault in indicating preparation
Sensitivity   20, 40, 60% absorption of ray by smoke
Reaction time   fast (~ 3s), slow (~ 10s)
Output relay max. switched voltage 176Vdc/125Vac
  max. switched current 1A
  max. switched power 30W/60VA
Range   (10 ÷ 100) m
Protected area   max. (100 x 14) m
Testing procedure   by means of a reducing shutter
Protection according to ČSN EN 55022   IP54
Radio screening degree according to ČSN 55022   B-class equipment
Setting of an address   by addressing preparation MHY 535, MHY 536 or adjustment preparation MHY 537, MHY 538
Cross-section of connectable wires   (0,2 ÷ 1,5) mm2
Weight   600g
Dimensions MHG 664 135 × 135 × 75 mm
  Reflex glass 100 x 100 mm for up to 50m
400 x 400 mm for up to 100m

 

Working conditions
The MHG 664 Linear smoke detector is intended for the interior of objects without occurrence of aggressive substances, and for places where its protection and climatic immunity conform, and where sudden temperature changes leading to dew and ice accretion don`t occur.
Working temperature range -25°C ÷ +70°C
Relative humidity max. 95% at +40°C
Atmospheric pressure 66 ÷ 106 kPa