MHY 734.031
MHY 734.031 base
The MHY 734.031 base is intended for connection with automatic fire detector LITES to control other equipment, eg fire sh

The MHY 734.031 base is intended for connection with automatic fire detector LITES to control other equipment, eg fire shutter.

The base is supplied with 24 V. AC or DC voltage. The voltage is rectified and stabilized to supply the detector. If the detector is activated to the alarm state, the relay closes in the socket. The independent changeover contact of the relay can be used to control eg a fire shutter. The reset is performed by disconnecting the power supply.

 

Technical parameters
Supply voltage 24V DC, AC ± 15 %
Self-consumption  
idle state max. 5 mA
alarm status max. 50 mA (including detector)
Connectable detectors MHG 231.070, MHG 331.071
Relay contact
current max.1 A
voltage max. 60 Vss / 30 Vst
Reset - resetting the base power stop for min. 2 s
Cross section of connectable wires 0,2 ÷ 1,5 mm²
Coverage according to ČSN EN 60529 IP 43 - location on the ceiling, IP 40 - another place
Dimensions ø98 × 28 mm

Mass

cca 95 g

 The product is intended for operation with safe equipment in the sense of ČSN EN 60950.

Working conditions
The base for fire shutters MHY 734.031 is designed for indoor areas of buildings without the presence of aggressive substances and wherever it meets its coverage and climate resistance and where there is no sudden temperature change leading to dew and icing.
Operating temperature range -25°C to +70°C
Relative air humidity max. 95% for +40°C
Atmospheric pressure 86 to 106 kPa